Precision Resistance Temperature Detectors in PT100 and PT1000 configurations. IEC 60751 compliant. 2-wire, 3-wire, and 4-wire constructions for aerospace, industrial, and cryogenic temperature measurement.
A Resistance Temperature Detector (RTD) operates on the principle that the electrical resistance of pure metals increases predictably with temperature. The sensing element — most commonly a platinum wire or thin-film platinum element — exhibits a near-linear resistance-temperature relationship governed by the Callendar-Van Dusen equation per IEC 60751.
The industry standard PT100 element exhibits a nominal resistance of 100.00 Ω at 0°C with a Temperature Coefficient of Resistance (TCR) of 0.003850 Ω/Ω/°C (the α=0.00385 European curve). PT1000 elements operate on the same principle at 1000 Ω nominal, offering reduced sensitivity to lead wire resistance in long cable runs.
Compared to thermocouples, RTDs deliver superior accuracy, better long-term stability, and improved repeatability — at the cost of slower response time and higher cost per assembly. For applications requiring measurement uncertainty below ±1°C with documented calibration traceability, RTDs are the preferred sensing technology.
| Parameter | RTD (PT100) | Thermocouple Type K |
|---|---|---|
| Temperature Range | -200 to +850°C | -200 to +1260°C |
| Accuracy (typical) | ±0.1 to ±0.3°C | ±0.5 to ±2.2°C |
| Stability (long-term) | Excellent | Good |
| Repeatability | ±0.1°C | ±0.5°C |
| Response Time | Slower (seconds) | Fast (ms–seconds) |
| Output Signal | Resistance (Ω) | Voltage (mV) |
| Self-Heating Error | Possible (4-wire eliminates) | None |
| Calibration Standard | IEC 60751 | IEC 60584 / ASTM E230 |
| Typical Cost | Higher | Lower |
| Best Application | Precision process control | High-temp, fast response |
27+ standard configurations available from stock or short-lead production. All configurations available with custom sheath lengths, termination styles, and special tolerances. Add to cart for standard configurations or request a quote for custom requirements.
Showing 6 of 27+ configurations. All configurations available with custom sheath materials, lengths, and terminations.
View All 27+ ConfigurationsThe number of lead wires determines how lead resistance error is handled in the measurement circuit. Selecting the correct configuration for your application is critical to achieving specified measurement accuracy.
Simplest construction. Lead wire resistance (RL) is included in measurement, introducing a systematic positive error of approximately +0.4°C per ohm of lead resistance. Acceptable only for short cable runs where lead resistance error is negligible relative to required accuracy.
The most common industrial RTD configuration. Uses a Wheatstone bridge circuit to compensate for lead wire resistance by assuming both lead wires are equal length and resistance. Provides adequate compensation for most industrial process applications with balanced lead runs. Error is reduced to the mismatch between the two leads.
Highest accuracy configuration. Uses a Kelvin (4-wire) sensing circuit where two wires source current and two wires sense voltage independently — completely eliminating lead wire resistance error regardless of lead length or temperature. Required for Class A tolerance verification, laboratory calibration, and aerospace measurement applications.
Per IEC 60751:2008 (the current governing standard for industrial platinum resistance thermometers), tolerance classes define the maximum permissible deviation of the RTD from the reference resistance-temperature relationship.
For aerospace applications, Class A is the minimum typically specified. Tighter 1/3 DIN or 1/10 DIN tolerances are available on special order. Contact our engineering team for custom tolerance specifications.
Request Custom Tolerance Quote| Class | Tolerance Formula | At 0°C | At 100°C | At 400°C |
|---|---|---|---|---|
| Class AA | ±(0.10 + 0.0017|t|)°C | ±0.10°C | ±0.27°C | ±0.78°C |
| Class A | ±(0.15 + 0.002|t|)°C | ±0.15°C | ±0.35°C | ±0.95°C |
| Class B | ±(0.30 + 0.005|t|)°C | ±0.30°C | ±0.80°C | ±2.30°C |
| Class C | ±(0.60 + 0.010|t|)°C | ±0.60°C | ±1.60°C | ±4.60°C |
| 1/3 DIN | ±(0.10 + 0.00167|t|)°C | ±0.10°C | ±0.267°C | ±0.767°C |
| 1/10 DIN | ±(0.03 + 0.0005|t|)°C | ±0.03°C | ±0.08°C | ±0.23°C |
|t| = absolute value of temperature in °C. Class AA valid from -50 to +250°C. Class A valid from -100 to +450°C.
RTD sensors are the preferred temperature sensing solution whenever measurement accuracy, long-term stability, and documentation traceability are critical requirements. Industries where these attributes are non-negotiable demand RTDs over thermocouples.
Custom Engineering InquiryAnswers to the most common engineering questions about RTD sensor selection, configuration, and specification. For application-specific guidance, contact our engineering team.
"PT" designates platinum as the sensing element material. "100" is the nominal resistance in ohms at 0°C (100.00 Ω). The PT100 sensing element exhibits a resistance that increases predictably with temperature at a coefficient of approximately 0.385 Ω per degree Celsius near 0°C, following the IEC 60751 standard relationship.
PT1000 elements are identical in principle, with 1000.00 Ω nominal at 0°C — ten times the resistance of a PT100. The higher resistance reduces the relative contribution of lead wire resistance to measurement error, which can be advantageous in long-lead-wire installations.
The alpha (α) value is the mean temperature coefficient of resistance of the platinum element, calculated as (R100 - R0) / (R0 × 100). The IEC 60751 standard specifies α = 0.003850 Ω/Ω/°C — commonly called "the 385 curve" or "DIN curve." This is the universal standard for industrial RTDs.
Older US specifications sometimes used α = 0.003902 (SAMA curve) or α = 0.003916. Thermometrics manufactures to the IEC 60751 α = 0.00385 standard by default. Custom alpha values are available — specify on your RFQ.
Self-heating (Joule heating) occurs because the measurement current flowing through the RTD element dissipates power as heat (P = I²R), artificially raising the element temperature above the medium temperature. For a PT100 at 1 mA excitation, self-heating power is approximately 0.1 mW — which can cause a +0.1 to +0.5°C error depending on thermal contact with the medium.
Minimization strategies: reduce excitation current (0.5–1.0 mA is typical), use a 4-wire Kelvin circuit to eliminate lead resistance and allow lower current, specify a thin-wall sheath for better thermal contact, and ensure adequate immersion depth to minimize axial conduction error.
Standard aerospace documentation includes: Certificate of Conformance (COC) to customer purchase order and applicable specifications, material certifications with heat/lot traceability, dimensional inspection records, and calibration data sheet with NIST traceability statement.
On request: First Article Inspection Report (FAIR) per AS9102, NIST-traceable calibration certificate with expanded uncertainty (k=2), special process certifications (welding, cleaning), and AS9100D quality plan. Specify documentation requirements on your RFQ.
Standard catalog configurations are available in quantities of one (1) with next-day shipping from stock. Custom configurations — non-standard sheath dimensions, special alloys, or unique terminations — typically have no minimum order quantity for production runs, though unit pricing improves at higher volumes.
Prototype lead time for new custom configurations is typically 2–3 weeks from approved drawing. Production lead time is 3–5 weeks for most custom assemblies. Rush production is available — contact us for AOG or expedited requirements.
Get a quote within one business day — same-day response on standard configurations.