Configuration4-wire (Kelvin) — 2 current leads + 2 voltage-sensing leads
Lead Resistance ErrorZero — independent of cable length and resistance
Measurement MethodForce current through outer leads; measure voltage across inner leads
Applicable StandardsIEC 60751 Class AA, A, B, C (all classes)
Minimum for Class AA4-wire required — 3 and 2-wire cannot achieve Class AA accuracy
Cable RunUnlimited — lead resistance fully cancelled by sensing circuit
Connector TypesTerminal head, mini TC connector, M12, bare leads
Sheath Materials316 SS, Inconel 600, Hastelloy C-276, PTFE
Element TypesPT100 or PT1000 per IEC 60751
DocumentationAS9100D COC + NIST-traceable cal cert available
Technical Notes
In a 4-wire Kelvin circuit, a precision current source forces a known current (typically 1 mA) through the outer two leads. The voltage is measured across the inner two leads using a high-impedance voltmeter. Since negligible current flows through the voltage-sensing leads, the lead resistance of the sensing pair has no effect on the measurement. This is the only RTD configuration that completely eliminates lead resistance error — it is mandatory for Class AA measurements.