IEC 60584 Type C — Thermocouple Data
Positive LegTungsten-5% Rhenium (W-5%Re)
Negative LegTungsten-26% Rhenium (W-26%Re)
Full Range0°C to +2315°C
Practical Range+200°C to +2315°C (vacuum/inert/hydrogen only)
Seebeck Coefficient~16.0 µV/°C at 1000°C; ~6.5 µV/°C at 2000°C
Class 1 TolerancePer ASTM E230 — not IEC 60584 standardized
Class 2 Tolerance±1.0% of reading above 425°C (ASTM)
Class 1 IEC RangeN/A — not IEC standardized (ASTM E230)
Class 2 IEC RangeN/A
Color Code (IEC)N/A (not IEC standardized)
Color Code (ANSI)White (+) / Red (–) (ANSI/ASTM)
Standard SheathTantalum or tungsten protection tubes
ConstructionMIMS (standard) or conventional; ungrounded, grounded, or exposed junction
DocumentationAS9100D COC + material certs standard; NIST-traceable cal cert on request
Application Notes
Type C (W5%Re/W26%Re) is NOT an IEC 60584-standardized type — governed by ASTM E230. Critically: tungsten-rhenium thermocouples oxidize catastrophically in air above 260°C. They must ONLY be used in vacuum, inert gas (argon, helium), or hydrogen atmospheres. The refractory metal wires are brittle at room temperature; handling requires care. Type C cannot be used at sub-zero temperatures. Contact Thermometrics engineering for application review before specifying Type C.