Simplest Configuration · Short Runs · PT1000 Recommended

2-Wire
RTD Configuration

Two-wire RTD is the simplest and lowest-cost RTD configuration — the measurement current path and voltage sensing path share the same conductors. Lead resistance appears directly as an error. Best paired with PT1000 to minimize lead resistance impact.

Technical Data

Specification Summary
Configuration2-wire — single pair carries both current and sense signal
Lead Resistance ErrorFull lead resistance adds to reading — both leads appear as RTD resistance
Error per Ω Lead (PT100)~0.26°C error per Ω of total lead resistance
Error per Ω Lead (PT1000)~0.026°C error per Ω of total lead resistance
Recommended ElementPT1000 for runs > 3 m; PT100 only where lead R is negligible
Max Practical Run (PT100)< 5 m with 0.5 mm² cable for < 1°C error
Max Practical Run (PT1000)< 50 m with 0.5 mm² cable for < 1°C error
Applicable ClassesIEC 60751 Class B and C practical; Class A only with short leads
Element TypesPT100 or PT1000
DocumentationAS9100D COC standard
Technical Notes
Two-wire RTD adds both lead resistances directly to the measured resistance. For PT100 at 25°C, the sensitivity is approximately 0.385 Ω/°C — meaning 0.385 Ω of lead resistance produces 1°C of positive reading error. 22 AWG copper wire has a resistance of approximately 0.0525 Ω/m; a 10 m run produces ~1.05 Ω total, causing ~2.7°C error on PT100. For PT1000 the same run causes only ~0.27°C error. Specify 2-wire only when cable run is known to be short or when a PT1000 element is used and run length is modest.

Common Applications

Thermostat and HVAC duct sensors with integral wiring
On-board machine temperature with direct sensor-to-PCB wiring
Short-run process temperature where PT1000 is used
Battery-powered dataloggers with local sensor mounting
Replacement sensors in existing 2-wire installations